You can download the manual for the S40 using the link below, you will need to register your details before accessing the file.
| Rating (kVA) |
10-15-20-30 |
40-60 |
80-100-120 |
160-200 |
250 |
| Capacity (kVA/KW) |
10/8, 15/12, 20/16, 30/24 |
40/32, 60/48 |
80/64, 100/80, 120/96 |
160/128, 200/160 |
250/200 |
| Dimensions HxWxD (mm) |
1470x560x835 |
1470x560x835 |
1470x825x835 |
1825x1220x925 |
1825x1220x925 |
| Weight (kg) |
310-385 |
440-510 |
669-745 |
1175 |
1300 |
| Input connection |
Hardwired |
| Output connection |
Hardwired |
| Battery |
Internal or external |
External |
| Operational |
| Nominal Input voltage (VAC) |
380, 400, 415 VAC three phase, neutral and earth Other input voltages and 60Hz input available as options |
| Input voltage range |
342 to 477 VAC |
| Operating frequency |
50 or 60 Hz (+-5%) |
| Input Power factor |
0,83 lag (nominal full load) ; 0,9 with filter |
| Input current distortion (THD) |
27% 6pulse rectifier , 10% 12pulse rectifier, 5% 12pulse rectifier with filter |
| Nominal Output voltage |
380, 400, 415 VAC three phase 4 wire, neutral may be earthed other voltages and 60Hz output available as options |
| Output voltage regulation |
±1% static; ±5% dynamic at 100% load change, <50 ms recovery time |
| Overload capacity |
125% for 10 min, 150% 5sec (online three-phase); 170% for 10 min, 2000% 5sec (online one-phase); 2000% for 20 msec (bypass), 130% continuous (bypass) |
| Efficiency (98% with Efficiency Optimiser) |
>90% |
>91% |
>91% |
>93% |
>93% |
| Option |
Parallel operation for increased capacity/parallel redundant, and hot-standby systems; isolation transformers, 12 pulse rectifiers, input harmonic filters, separate input terminals for bypass, full capacity static bypass, separate external manual bypass, external battery cabinets, transformers/autotransformers for voltage adaption, top cable entry bottom cable entry, frequency converters for 60Hz and 400Hz output |
| User interface mimic panel |
| LCD-display |
LCD display showing status, metering, performance monitoring , alarms and event log. |
| LED's |
LEDs + mimic display of power flow |
| Standard comm-unication ports |
1xRS232 for local support; IBM AS400 interface relays; 2xrelay change over contacts: EPO signal, General UPS alarm; Remote Emergency Power Off |
| Optional |
RS232 extension, SNMP/WEB, Remote UPS display panel, 9 relay Outputs; additional metering and displays |
| Environmental |
| Operating temperature |
0°C to +40°C |
| Storage temperature |
-25°C to +85°C |
| Altitude |
< 1000 m |
| Audible noise at 1 metre (dBA) (According to ISO 3747) |
58 |
60 |
61-62 |
70 |
70 |
| Certification |
| Markings |
CE |
| Safety |
EN 50091-1 |
| EMC |
EN 50091-2 |
|
|