S10 - Technical Data

System Data

System Data UPS Power Rating
10 15 20 25
System configuration On-line
Normal input voltage 3x380/400/415 V Tolerance ±10%
Normal input frequency 50 (60) Hz Tolerance: ±5%
Normal output Vvoltage 220 V, 230 V, 240 V
Normal output frequency 50 (60) Hz
Output volt. dist. (THD), linear load
Output volt. dist. (THD), non linear load
< 1.5%
< 4% (CF <= 3:1)
Output voltage tolerances
static
dynamic
 
± 1%
± 10%
Output frequency tolerance
mains synchronisation (adjustable)
free running
 
± 0.5/1/1.5/2 Hz
±0.01%
Rated output power (p.f=0.8lag.)
[kVA]
10 15 20 25
Rated output power (p.f=1.0)
[kW]
8 12 16 20
System efficency at rated load
[%]
90 90 91 91
Losses at nominal load
[kW]
1 1.5 1.8 2.2
Overload capability
Inverter
Static bypass switch
 
125% 10 minutes, 150% 1 minute
2000% full load for 20ms, 200% 1 minute,
150% continually
Permissible inverter output voltage variation
for bypass switching
 
±15% (adjustable)
Design standards IEC, VDE, SEV
Insulation test for 60 sec. 2.0 kV
Voltage transient protection Complies woth the VDE 0160
Enclosure IP 30 acc. to DIN 40050 excl air exit
Ambient tempreture
for operation
for storage
 
0 to 40°C
-20 to 85°C (excl. battery)
Permissible relative humidity 95%
Permissible altitude above sea level at full load 1500m Higher altitudes require power derating or increased cooling
EMC Compatibility Complies with EN 50091-2 (1996)
Audible noise level < [db(A)] 60 60 60 60

Rectifier Data

Rectifier Data UPS Power Rating
10 15 20 25
Input Voltage
Tolerance
with reduced output DC-voltage
refer to system date
-10%
-20%
Input frequency
Tolerance
refer to system data
±5%
Rated input power with charged battery
[kVA]
10.9 16.3 21.8 27.2
Rated input current with charged battery (at 380V)
[A]
17 25 34 42
Maximal input power
(rated output power and max. recharging current) [kVA]
13.6 20.4 27.2 34.0
Maximal input current at max. input power (at 380V)
[A]
21 31 41 51
Input power factor
(100% load, 380V input voltage)
~0.8 lagging
Output control characteristic I/U characteristic
Rated output voltage 432 VDC
Range of adjustment of floating voltage ±25%
Soft start 2 seconds
Tolereance of floating voltage 1%
Voltage Ripple with battery disconnected RMS 1%
Max. battery discharge current
(VDC = 320V, nominal load)
[A]
27 41 54 69
Max. battery charger current
at rated load
[A]
5 7.5 10 12.5
Battery charge current limitation complies with battery manufacturer's recommendations, standard setting app.10% of rated 10h battery capacity

Battery Data

Battery Data UPS Power Rating
10 15 20 25
Capacity
[Ah]
24 24 24 24
Autonomy times at full load
24Ah
38Ah
65Ah
[min]
 
30
50
100
 
20
33
67
 
12
22
45
 
6
12
25
Number of cells (standard)
Lead open
Sealed lead maintenance free
Ni-Cd
 
192
192
300
Floating voltage at 20°C
Lead open - 2.25 V/Cell
Scaled lead - 2.27 V/Cell
Ni-Cd - 1.42 V/Cell
[VDC]
 
432
436
426
Minimum battery voltage
lead - 1.68 V/Cell
Ni-Cd - 1.06 V/Cell
[VDC]
 
322
320
Recommended charging current 10% of rated 10h battery capacity
Protections - batt. protection disconnector switch *1)
- automatic shutdown of the inverter at min. DC-voltage
Permissible DC voltage range
[VDC]
min. 320 ............ max. 462
Floating voltage adjustment range ±25% of nominal value (minimal)
Ambient tempreture follow battery manufacturer's instructions
1) battery disconnector fuse for free standing battery operation

Inverter Data

Inverter Data UPS Power Rating
10 15 20 25
Permissible input DC-voltage range 320-480 VDC
Input power at rated load
[kW]
8.7 13 17.4 21.8
Inverter input current at 320 VDC and rated load
[A]
27 41 54 69
Nominal output current at rated load (380V, p.f.=0.8)
[A]
45.5 68.2 91 113.6
Nominal output current
(380V, p.f.=1.0)
[A]
36.4 54.5 77.7 90.9
Efficiency at rated load
[%]
92 92 92.5 93
Load power factor range
at nominal load
at reduced load
 
0.7=0.8 lag.
0.5 lag.-0.5 Lead.
Output voltage refer to system data
Output voltage distortion THD refer to system data
Voltage adjustment range ±5% of programmable nominal value
Voltage tolerances
static
dynamic
 
±1%
±10%
Voltage transistent recovery time <=40ms to within ±2% of output voltage
The unit is short circuit proof
(Short circuit current)
150% of nominal current
Frequency adjustment range ±2Hz
Max frequency variation during
synchronisation
±1Hz/sec.
 